✎ Electrical Technology

Periodic Inspection and Maintenance of Solid Soft Starters

← Back to Electrical Technology

高压固态软启动器定期检查与维护
Periodic Inspection and Maintenance of Solid Soft Starters

在规定的技术条件和使用范围内正确运行时,软启动器通常具有较高的可靠性和较长的使用寿命,日常维护需求相对较少。为确保设备安全、稳定运行,仍应根据运行环境、设备状态及制造商要求,定期检查和维护以下项目。

When operated correctly and within its specified technical limits, a soft starter is generally reliable and has a long service life, with relatively low routine maintenance requirements. Nevertheless, the following items should be inspected and maintained periodically in accordance with the operating environment, equipment condition, and the manufacturer’s instructions to ensure safe and reliable operation.

 

维护工作必须由具备相应资质和经验的专业人员实施,或在其现场指导下进行。维护前,应按照现场安全规程执行停电、隔离、上锁挂牌(LOTO)及验电程序。主电源和控制电源均须断开,并确认设备已无电。对于可能储存电能的电容器及其他部件,应按照制造商规定等待放电并确认安全后,方可作业。严禁在未采取充分安全措施的情况下进行维护。

Maintenance must be carried out by qualified and experienced personnel, or under their direct supervision. Before maintenance, follow the site’s safety procedures for shutdown, isolation, lockout/tagout (LOTO), and verification of absence of voltage. Both the main power supply and the control power supply must be disconnected, and the equipment must be confirmed de-energized. For capacitors and other components that may store energy, observe the manufacturer’s specified discharge time and verify that they are safe before work begins. Never perform maintenance without adequate safety precautions.

安全提示 / SAFETY NOTICE
所有维护工作开始前,必须由专业人员完成断电、隔离、上锁挂牌和验电。具体操作以设备制造商说明书及现场安全规程为准。
Before any maintenance work, qualified personnel must isolate the equipment, apply lockout/tagout, and verify the absence of voltage. Always follow the manufacturer’s instructions and site safety procedures.

 

  1. 设备清洁 / Equipment Cleaning

定期检查软启动器柜体内部及元器件表面是否清洁。灰尘、污物或导电性沉积物可能降低绝缘性能,并导致以下问题:

Periodically inspect the inside of the soft starter enclosure and the surfaces of its components. Dust, dirt, or conductive deposits may impair insulation performance and lead to the following problems:

一次回路爬电、放电或电弧,严重时可能引发短路故障。

Creepage, discharge, or arcing in the main circuit, potentially resulting in a short circuit.

二次回路绝缘性能下降、漏电或短路,导致控制异常。

Degraded insulation, leakage, or short circuits in the control circuit, resulting in abnormal operation.

散热器表面及风道积尘,影响散热,导致晶闸管温升过高,并可能触发过温保护或损坏晶闸管。

Dust accumulation on heat sinks and in air passages may impair cooling, increase thyristor temperature, trigger overtemperature protection, or damage the thyristors.

 

维护方法 / Recommended Maintenance

清洁前确保设备已按安全规程断电并确认无电。使用清洁、干燥的软毛刷清除灰尘。必要时,可使用干燥、洁净且压力适当的压缩空气清洁印制电路板(PCB),但应避免气流或压力损伤元器件。顽固污渍应使用制造商认可的清洁剂和方法处理。清洁后确认设备完全干燥,再恢复运行。

Before cleaning, isolate the equipment in accordance with the safety procedure and verify that it is de-energized. Remove dust with a clean, dry, soft-bristled brush. If necessary, use clean, dry, suitably regulated compressed air to clean printed circuit boards (PCBs), taking care not to damage components. Remove stubborn contamination only with cleaning agents and methods approved by the manufacturer. Ensure that the equipment is completely dry before returning it to service.

 

  1. 凝露与防潮 / Condensation and Moisture Control

在高湿度季节或容易发生温差变化的环境中,应增加检查频次,确认柜内是否存在凝露或受潮现象。凝露可能降低绝缘性能,并造成以下问题:

In humid seasons or environments subject to significant temperature variations, increase inspection frequency and check the enclosure for condensation or moisture. Condensation may impair insulation performance and cause the following problems:

一次回路爬电、放电或电弧,严重时可能引发短路。

Creepage, discharge, or arcing in the main circuit, potentially resulting in a short circuit.

二次回路绝缘性能下降、漏电或短路,造成控制异常。

Degraded insulation, leakage, or short circuits in the control circuit, causing abnormal operation.

金属部件腐蚀。

Corrosion of metallic components.

维护方法 / Recommended Maintenance

如发现凝露,应先查明原因并在安全条件下彻底干燥。可根据现场情况使用适当的干燥设备或除湿机降低配电室湿度;必要时,在柜内配置制造商认可的加热器或防凝露装置。不得在设备带电或未确认安全的情况下使用热风枪等工具直接处理内部元件。

If condensation is found, identify the cause and ensure the equipment is thoroughly dried under safe conditions. Depending on site conditions, use suitable drying equipment or a dehumidifier to reduce room humidity. If necessary, install a manufacturer-approved space heater or anti-condensation device inside the enclosure. Do not use a heat gun or similar tool directly on internal components while the equipment is energized or has not been confirmed safe.

 

  1. 通风与散热系统 / Ventilation and Cooling System

对于配置散热风机的软启动器,应定期检查风道是否畅通、过滤网是否堵塞,以及风机运行是否正常。风道堵塞或风机故障会降低散热能力,使晶闸管温升增加,可能导致过温保护动作或器件损坏。

For soft starters equipped with cooling fans, periodically check that the air passages are clear, the filters are not blocked, and the fans operate correctly. Blocked air passages or faulty fans reduce cooling performance and increase thyristor temperature, potentially causing overtemperature protection to operate or components to fail.

维护方法 / Recommended Maintenance

及时清除风道和过滤网上的积尘及异物。若风机不转、转速明显异常或出现异常噪声,应检查并按制造商要求更换。替换风机应符合原设备要求,至少确保安装尺寸、额定电压、接线方式及风量等参数匹配;不得使用风量低于原配置的风机。

Remove dust and foreign matter from air passages and filters promptly. If a fan does not run, operates at an abnormal speed, or makes unusual noise, inspect it and replace it in accordance with the manufacturer’s instructions. The replacement fan must meet the original equipment requirements, including mounting dimensions, rated voltage, wiring, and airflow. Do not use a fan with a lower airflow rating than the original.

 

  1. 连接件与紧固件 / Electrical Connections and Fasteners

定期检查主回路、控制回路及柜内其他电气元件的连接是否牢固。连接松动可能导致接触电阻增大、连接点过热,严重时可能造成烧蚀、熔断或邻近绝缘材料老化;控制回路接触不良还可能引起设备误动作或运行异常。

Periodically check that connections in the main circuit, control circuit, and other electrical components inside the enclosure are secure. Loose connections may increase contact resistance and cause overheating. In severe cases, they may lead to burning, melting, or accelerated ageing of nearby insulation. Poor contact in the control circuit may also cause malfunction or abnormal operation.

维护方法 / Recommended Maintenance

设备运行一段时间后,紧固件可能因振动或热循环而松动。发现松动时,应按照制造商规定的紧固力矩重新紧固。对于有明确力矩要求的连接点,必须使用合适的工具并遵循说明书。原文件建议:设备投运后1–6个月进行一次全面检查和紧固,之后每1–2年检查一次;实际周期应结合制造商要求、运行环境及检查结果确定。同时检查焊接点是否存在虚焊、脱焊或腐蚀。

Fasteners may loosen over time due to vibration or thermal cycling. If a loose connection is found, retighten it to the torque specified by the manufacturer, using suitable tools. The source document recommends an initial comprehensive inspection and retightening 1–6 months after commissioning, followed by inspections every 1–2 years. The actual interval should be determined by the manufacturer’s instructions, operating conditions, and inspection results. Also check soldered joints for poor soldering, detached joints, or corrosion.

 

  1. 导线与电缆 / Wiring and Cables

定期检查柜内主回路和控制回路的导线及电缆,重点查看是否存在绝缘老化、变色、炭化、龟裂、磨损或其他机械损伤。导线绝缘损坏可能导致主回路爬电、放电或短路,也可能造成控制回路漏电、短路及控制异常。

Periodically inspect the wires and cables in the main and control circuits. Pay particular attention to insulation ageing, discoloration, carbonization, cracking, abrasion, and other mechanical damage. Damaged insulation may cause creepage, discharge, or short circuits in the main circuit, as well as leakage, short circuits, or control malfunctions in the control circuit.

维护方法 / Recommended Maintenance

发现绝缘老化或损伤时,应由专业人员评估并及时更换符合原设计要求的导线或电缆。不得仅因损伤程度较轻而忽略处理。

If insulation ageing or damage is found, qualified personnel should assess the condition and replace the affected wire or cable promptly with one that meets the original design specifications. Do not ignore damage merely because it appears minor.

 

  1. 运行环境 / Operating Environment

如果设备周围的运行环境发生明显变化,应评估其对软启动器的影响,并采取适当的防护措施。例如,粉尘增加时,应考虑改善柜体密封、配置适当的空气过滤装置;存在腐蚀性气体或潮湿环境时,应评估防腐、防潮及绝缘防护措施。

If the operating environment changes significantly, assess the impact on the soft starter and implement appropriate protective measures. For example, if dust levels increase, consider improving enclosure sealing and installing suitable air filtration. Where corrosive gases or high humidity are present, assess the need for corrosion protection, moisture control, and enhanced insulation protection.

维护方法 / Recommended Maintenance

同时关注环境温度、通风条件、振动及其他可能影响设备运行的因素。采取的措施应符合设备防护等级和制造商要求。

Also monitor ambient temperature, ventilation conditions, vibration, and any other factors that may affect equipment operation. All protective measures should comply with the equipment’s enclosure rating and the manufacturer’s requirements.

 

  1. 电气元器件 / Electrical Components

定期检查软启动器及其配套柜内的接触器、继电器、开关及其他电气元件,重点检查触头、衔铁和机械机构的状态。

Periodically inspect the contactors, relays, switches, and other electrical components in the soft starter and its associated enclosure, paying particular attention to the condition of contacts, armatures, and mechanical mechanisms.

按照制造商说明书检查触头是否存在烧蚀、严重磨损或污染。

Inspect contacts for burning, excessive wear, or contamination in accordance with the manufacturer’s instructions.

按照制造商技术文件检查真空接触器的触头开距及相关机械参数是否符合要求。

Check whether the contact gap and relevant mechanical parameters of vacuum contactors meet the specified requirements.

对磨损或损坏的触头、衔铁及其他部件进行维修或更换。

Repair or replace worn or damaged contacts, armatures, and other components.

根据制造商规定的寿命、操作次数或检查结果,更换起动接触器、继电器等易损元件。

Replace starting contactors, relays, and other wear components according to the manufacturer’s specified service life, operating count, or inspection results.

检查元器件是否存在过热痕迹、变色、异味或其他损坏迹象。

Check components for signs of overheating, discoloration, unusual odor, or other damage.

维护方法 / Recommended Maintenance

不得擅自使用砂纸打磨触头,以免损伤触头表面镀层或改变接触特性。清洁、调整和更换工作应遵循元器件制造商的维护要求。

Do not sand contact surfaces unless expressly permitted by the component manufacturer, as this may damage contact coatings or alter contact characteristics. Cleaning, adjustment, and replacement must follow the component manufacturer’s maintenance instructions.

 

  1. 保护功能 / Protection Functions

至少每年检查一次各保护装置及保护功能,包括动作逻辑、动作顺序和整定值,确认其符合设计要求及现场保护配合方案。

At least once a year, inspect the protection devices and functions, including their operating logic, sequence, and settings, to verify that they comply with the design requirements and the site’s protection coordination scheme.

维护方法 / Recommended Maintenance

保护功能测试和整定值调整必须由具备资质的专业人员执行,并做好测试记录。若制造商或项目技术文件规定了更严格的周期,应按其要求执行。

Protection testing and setting adjustments must be carried out by qualified personnel, with test results properly documented. Follow any shorter inspection intervals specified by the manufacturer or project documentation.

 

  1. 均流性能 / Current-Sharing Performance

对于采用多支路功率器件并联运行的大功率软启动器,应定期检查各并联支路的电流分配情况。原文件要求均流系数不低于0.7;如低于该值,应检查母排、快速熔断器及其连接点是否松动,并检查晶闸管等功率器件的性能是否异常。

For high-power soft starters with multiple parallel branches of power devices, periodically check current distribution among the parallel branches. The source document specifies a current-sharing coefficient of not less than 0.7. If the value is below this threshold, inspect the busbars, fast-acting fuses, and their connections for looseness, and check the thyristors and other power devices for abnormal performance.

维护方法 / Recommended Maintenance

均流系数的定义、测量方法及允许偏差应以设备制造商的技术文件为准。检查和测量应在规定的安全条件下进行。

The definition, measurement method, and permitted tolerance of the current-sharing coefficient must be confirmed against the equipment manufacturer’s technical documentation. Inspection and measurement must be performed under the specified safe conditions.

 

  1. 电位器、按钮及操作元件 / Potentiometers, Push Buttons, and Operating Devices

定期检查电位器、按钮、选择开关及其他操作元件,确认其动作正常、接触可靠,接线无松动或断线。发现接触不良、动作异常或部件损坏时,应及时处理或更换。

Periodically inspect potentiometers, push buttons, selector switches, and other operating devices to ensure correct operation, reliable contact, and secure wiring. Any poor contact, abnormal operation, loose connection, or damaged component should be addressed promptly.

维护方法 / Recommended Maintenance

清洁电位器或触点时,只能使用元器件制造商认可的清洁剂和方法。不得使用汽油等易燃溶剂。对腐蚀、磨损严重或无法可靠修复的操作元件,应及时更换。

When cleaning potentiometers or contacts, use only cleaning agents and methods approved by the component manufacturer. Do not use gasoline or other highly flammable solvents. Replace operating devices that are severely corroded, worn, or cannot be restored to reliable operation.

维护周期说明 / Maintenance Schedule

本文列出的检查项目和周期为一般性维护建议。实际维护计划应以软启动器制造商的最新版说明书、项目技术规范、设备运行条件及当地安全法规为准。任何检查周期、测试方法或更换要求如存在差异,应优先执行制造商和项目文件的明确规定。维护完成后,应记录检查结果、发现的问题、采取的措施及更换的部件。

The inspection items and intervals in this document are general maintenance recommendations. The actual maintenance schedule must comply with the latest soft starter manufacturer’s manual, project specifications, operating conditions, and applicable local safety regulations. Where inspection intervals, test methods, or replacement requirements differ, the explicit requirements of the manufacturer and project documentation take precedence. After maintenance, record the inspection results, defects identified, corrective actions taken, and components replaced.

软启动器定期检查与维护 | Periodic Inspection and Maintenance of Soft Starters